RAY Egelhof - "Low-NOx" Gas burners "EGLN" - series
RAY Egelhof - "Low-NOx" Gasburners “EGLN” series are industrial duobloc burners.
RAY Egelhof - “Low-NOx” Gasburners "EGLN" series achieve NOx values operating with natural gas < 80 mg/kWh. Compliance with the limit values is always system-dependent. Key influencing factors include the respective combustion chamber geometry, the cross-sectional load and the firing system (3-pass / through-burning principle). Guaranteed values can only be issued in conjunction with predefined boundary conditions (e.g. combustion chamber load, combustion air temperature, humidity, heat transfer medium temperature, measurement tolerances, etc.).
They are built according to a modular principle and consist of the burner, a windbox, a separately installed combustion air fan, fuel supply line(s) and control system.
RAY Egelhof - “Low-NOx” Gasburners "EGLN" series cover a capacity range from 432 kW (1,474 MBTU) - 22.000 kW (63,477 MBTU).
RAY Egelhof - “Low-NOx” Gasburner “EGLN” - series are very versatile and can use all technical combustible gases, biogases, hydrogen, LPG and process gases. Separate or parallel combustion of gaseous fuels is possible.
The digital combustion management system that is used as standard (other options are available on request) simplifies the operation, monitoring and maintenance of the burner.
For further information, please contact us - our team will be happy to support you!
Key data: RAY Egelhof - "Low-NOx" Gasburner "EGLN"-series
Applications | LTHW-boilers, HTHW-boilers, Thermal fluid heaters, Steam-boilers, Heat generators |
Fuels | all technical combustible gases, biogases, hydrogen, LPG and process gases, separately or simultaneously |
Sizes | 10 Sizes |
Operating range | 432 up to 22.000 kW |
Preheating | max. 250°C |
Turndown | 1:10 |
Key dimensions at a glance (for download)
Burner types EGLN 150 - 700 Cross section
Burner types EGLN 800 - 1500 Cross section
Burner rating /-weight and -dimensions
Model | Rating min. | Rating max. | Windbox with air damper Type |
Windbox with air damper unit Type |
Weight burner with windbox | ØA | J/L | ØC | H | I |
kW MBTU |
kW MBTU |
DLV | SLV | kg | mm | mm | mm | mm | mm | |
EGLN 150 |
432 1,474 |
1.744 5,951 |
35 | 15 | ca. 155 | 638 | 442 | 314 | 90 | 195 |
EGLN 250 |
700 2,388 |
2.907 9,919 |
35 | 25 | ca. 154 | 638 | 442 | 314 | 90 | 195 |
EGLN 350 |
930 3,173 |
4.070 13,887 |
35 | 35 | ca. 154 | 638 | 442 | 314 | 90 | 195 |
EGLN 500 |
975 3,327 |
5.814 19,837 |
70 | 50 | ca. 234 | 750 | 532 | 429 | 102 | 254 |
EGLN 600 |
1.165 3,975 |
6.977 23,806 |
70 | 60 | ca. 233 | 750 | 532 | 429 | 102 | 254 |
EGLN 700 |
1.280 4,367 |
8.139 27,770 |
70 | 70 | ca. 233 | 750 | 532 | 429 | 102 | 254 |
EGLN 800 |
1.400 4,777 |
9.302 31,738 |
100 | 80 | ca. 327 | 900 | 670 | 454 | 258 | 334 |
EGLN 1000 |
1.570 5,357 |
11.628 39,675 |
100 | 100 | ca. 326 | 900 | 670 | 454 | 258 | 334 |
EGLN 1250 |
1.860 6,346 |
14.535 49,593 |
125 | 125 | ca. 379 | 900 | 670 | 454 | 258 | 334 |
EGLN 1500 |
2.325 7,933 |
18.604 63,477 |
150 | -/- | ca. 431 | 900 | 670 | 454 | 258 | 334 |
General product features
- Modular principle
- Robust construction
- Durability
- Reliability
- Maintenance friendly
- Simultaneous combustion of several gases